Evaluasi Indeks Polaritas (PI) sebagai Indikator Keandalan Isolasi Kabel pada Sistem Pressurized Fan di Gedung Bertingkat PT XYZ

Authors

  • Arifin Hidayat Program Studi Program Profesi Insinyur, Fakultas Biosains, Teknologi, dan Inovasi, Universitas Katolik Indonesia Atma Jaya
  • Maria Angela Kartawidjaja Program Studi Teknik Elektro, Fakultas Biosains, Teknologi, dan Inovasi, Universitas Katolik Indonesia Atma Jaya

DOI:

https://doi.org/10.25170/jpk.v2i03.6928

Keywords:

Polarization Index, Pressurized Fan, Insulation Test

Abstract

 The reliability of electrical systems and mechanical equipment, such as
Pressurized Fans is critical for ensuring safety and operational
continuity in high-rise buildings, particularly in emergency stairwells.
This study focuses on Polarization Index (PI) testing to evaluate cable
insulation conditions in Pressurized Fan at PT XYZ. The methodology
includes initial functional testing, literature review, automated control
panel design, and system performance evaluation. Test results revealed
that while insulation resistance (IR) values met standards (>25 MΩ), low
PI values (<1.0) indicated insulation degradation, causing frequent
tripping of the Pressurized Fan. The implemented solutions involved
replacing the cable installation and designing a more reliable control
panel. Post-improvement, the system operated optimally and complied
with safety standards such as SNI 03-1746-2000 and NFPA 92A. This
study highlights the importance of preventive maintenance through
regular PI testing to prevent system failures and ensure building
occupant safety.

References

L. Yuliana, A. S. Mappangile, B. Amiricano (2021), “Analisis Kesesuaian Tangga Darurat pada Gedung A di Universitas Balikpapan” Program Studi Keselamatan dan Kesehatan Kerja Universitas Balikpapan. Jurnal Keselamatan, Kesehatan Kerja dan Lindungan Lingkungan 7(2) : 474 - 483

M. H. Indra, Y. Suzantry H., I. Priyadi (2022), “Pengujian Tahanan Isolasi Pada Transformator Distribusi 160 kVA Di PT PLN (PERSERO) UP3 Bengkulu” Program Studi Teknik Elektro Universitas Bengkulu. Jurnal Amplifier : Jurnal Ilmiah Bidang Teknik Elektro dan Komputer 12(2) : 8-15

A. A. R. Irwanto, Hermawan (2024), “Metoda Sederhana untuk Memperbaiki Kinerja Motor Listrik 3 Fasa berdasarkan Insulation Resistance Test” Program Studi Teknik Elektro Universitas Pendidikan Indonesia. Jurnal Pengelolaan Laboratorium Pendidikan, 6(1) : 55-62

IEC (2010), “Rotating Electrical Machine – Part 1 Rating and Perfromance”, IEC 60034-1.284

IEEE (2000), “IEEE Recommended Practice for Testing Insulation Resistance of Rotating Machinery”, IEEE Std 43-2000 [Online]. Tersedia: https://standards.ieee.org/ieee/43/190/. Diakses tanggal 02 Mei 2025.

H. Abdillah, M. A. Baihaqi, L. Hakim., A. Analisa, H. Arista (2023), “Analisis Pengukuran Tahanan Isolasi dan Indeks Polaritas pada Motor 3 Fasa” Program Studi Teknik Elektro & Teknik Informatika Universitas Panca Marga.

Atika Rossydina P. P. , Heru Sufianto (2018) , "Sistem Proteksi Kebakaran pada Gedung UKM Universitas Brawijaya Malang" Fakultas Teknik Universitas Brawijaya. Jurnal Mahasiswa Departemen Arsitektur 6(1) : 1-11

Kamula Luna Zulfardi , Andreas F. V. Roy (2023), "Penilaian Sistem Proteksi dan Kesesuaian Jalur Evakuasi Kebakaran pada Gedung PPAG 2 Universitas Katolik Parahyangan". Journal of Sustainable Construction 2(2) : 22-37

Yesi Aprilia Savitri (2017), "Analisa Faktor Penghambat Proses Ev2(2) akuasi di Apartemen X", Fakultas Teknik Universitas Negeri Jakarta.

Badan Standarisasi Nasional (2000) “SNI 03-1736-2000 tentang Tata Cara Perencanaan Sistem Proteksi Kebakaran pada Bangunan Gedung”.

Sin-Dong Kang, Jae-Ho Kim (2020), "Investigation on the Insulation Resistance Characteristics of Low Voltage Cable" Department of Fire & Disaster Prevention Engineering, Daejeon University