Evaluasi Kondisi Panel Listrik dan Pengembangan Sistem Pemantauan Berbasis Barcode dalam Penyusunan Program Pemeliharaan pada Rumah Sakit ABC
DOI:
https://doi.org/10.25170/jpk.v3i04.8129Keywords:
Electrical panel, Reliability, Panel Maintenance, BarcodeAbstract
Electrical panels in hospitals play a vital role in ensuring the continuity and reliability of medical services. However, the maintenance of electrical panels at ABC Hospital has not been carried out optimally and still relies on a manual, non-integrated reporting system, which potentially increases the risk of operational disruptions. This study aims to evaluate the condition of existing electrical panels and to develop a barcode-based monitoring system to support the preparation of an effective and integrated maintenance program. The methods employed include data identification and collection, panel condition evaluation through visual inspection and temperature measurement using a thermal camera, risk-based reliability analysis, and the design of a barcode-based monitoring system. The results show that there are 43 electrical panel cells in Building R, all of which require cleaning, and 8 panels are identified as priority units requiring further maintenance actions. The development of a barcode-based system enables integrated and easily traceable maintenance documentation. This study emphasizes that scheduled maintenance can improve the reliability of electrical systems and ensure the safety and continuity of medical services in hospitals.
References
Aksan, Akhmad, S. S., & Aminah, N. (2022). Evaluasi kondisi peralatan elektrikal gedung Kampus 1 PNUP menggunakan metode infrared thermography. Prosiding Seminar Nasional Penelitian & Pengabdian Kepada Masyarakat (pp.83-88). Makasar: Politeknik Negeri Ujung Pandang.
Azzahra, Z. F., & Suakanto, S. (2025). A barcode-based medical asset management system with integrated monitoring in hospitals. JUSIFO (Jurnal Sistem Informasi), 11(1), 21–30.
Ahmad Paid, Kusyanto, Eko Yuli Rustanto & Suhatno. (2017). Pemantauan Thermography Inframerah dalam Pemeliharaan Instalasi Listrik Fasilitas Sarana Dukung IEBE. Pusat Teknologi Bahan Bakar Nuklir, Kawasan PUSPIPTEK. ISSN 1979-2409. Tangerang.
Badan Standardisasi Nasional & Panitia Teknik PUIL. (2011). Persyaratan Umum Instalasi Listrik (PUIL) 2011. Jakarta: Badan Standardisasi Nasional.
Kementerian Kesehatan Republik Indonesia. (2022). Peraturan Menteri Kesehatan Republik Indonesia Nomor 40 Tahun 2022 tentang Persyaratan Teknis Bangunan, Prasarana, dan Peralatan Kesehatan Rumah Sakit. Jakarta: Kementerian Kesehatan Republik Indonesia.
Kusmantoro, Adhi & Sukamta, Sri. (2013). Pemeriksaan Kondisi Peralatan Mekanikal dan Elektrikal Gedung Menggunakan Metode Infrared Thermography. Jurnal Teknik Elektro UNNES, 5(1), 6 – 11.
National Fire Protection Association. (2019). NFPA 70B: Recommended Practice for Electrical Equipment Maintenance. Quincy, MA: National Fire Protection Association.
Palembangan, H. S., Yuliana, L., Rekoyoso, B., & Zulfikar, I. (2026). Inspeksi dan penilaian kelayakan pada panel listrik di tempat kerja berdasarkan standar K3 listrik di PT XCV. Jurnal Pengabdian Masyarakat, 5(1), 69 – 77.
Shobah, M.N. & Anshory, I. (2024). Pioneering Maintenance Strategies for Enhanced Reliability of Low Voltage Switchboards (Merintis Strategi Pemeliharaan untuk Meningkatkan Keandalan Switchboard Tegangan Rendah). Seminar Nasional & Call Paper Fakultas Sains dan Teknologi (SENASAINS 7th) (pp. 346-350). Sidoarjo: Universitas Muhammadiyah Sidoarjo.
Syahputra, H. (2020). Pemeliharaan komponen panel listrik sebagai pengontrol power supply di CV Delta Power Listrindo. Laporan Kerja Praktik, Program Studi Teknik Elektro. Medan: Universitas Medan Area.